Introduction
|
KID Neuro is middle range PLC with up to 96 local I/O
- Scan cycle of the user program (reaction time) - Depends from the size of the user program. Typically from 3 ms up to 10 ms.
- Size of the basic user program - About a 1000 Ladder elements memory (contacts, coils, timers etc.);
- Wide range of function blocks - add, subtract, move, block move, compare, drums, timers, reverse counters, shifts & rotates, matrix operations, approximation;
- Built - in blocks for real numbers mathematics;
- Built - in 8 PID's; IEC 61131 - 3 programming (KID Neuro PLC's Programmer);
- IEC 1131 electromagnetic compatibility;
- Communications - RS232/RS485 and LonWorks;
- Download Programs directly via LonWorks network;
- Fast (interrupt) program ( 50 mS reaction ) - 500 bytes (about a 60 steps).
- High speed counter inputs – 2
- WATCHDOG output with open collector – 1
- Modular construction
|
| Specifications |
Digital Inputs (KIDDI24)
- Number of input channels for one module: 8
- Nominal Input Voltage - 24V DC (up to 30mA)
Digital Outputs with MOSFET high side driver (KIDDO24)
- Number of output channels for one module: 8
- Nominal Outputs Voltage Supply - 24V DC
- Commutation Voltage - 24V DC (1A)
- Protection short circuit, over voltage and over temperature shutdown
Digital Outputs with relay (KIDDRY)
- Number of output channels for one module: 8
- Nominal Outputs Voltage Supply - 24V DC
- Commutation Voltage - up to 220V DC, up to 220V AC (2A)
Digital Outputs with triac (KIDDO220)
- Number of output channels for one module: 8
- Nominal Outputs Voltage Supply - 24V DC
- Commutation Voltage - 220V AC (100mA)
Analog Inputs (KIDAI)
- Number of input channels for one module:
- 5 single-ended
- 3 differential inputs
- Voltage Range: ±80mV, 0-2V
- Current Range: 0-20mA, 4-20mA
- Resistance:
- 0-2000W (RTD: Pt100, Pt500, Pt1000)
- Linear or successive approximation
Analog Outputs (KIDAO)
- Number of output channels for one module: 4
- Nominal Voltage Supply - 24V DC
- Output Ranges
- Voltage - 0 up to 5V, 0 up to 10V
- Current - 0 up to 20mA, 4 up to 20mA, 0 up to 24mA
|
| General Specifications |
|
Nominal: +24VDC/ 120mA (for processor part only)
- Voltage Range: 18V to 35VDC
- Operating temperature: -20°C ~ +80°C
- Storage temperature : -40°C ~ +85°C
- Protection – IP 20
- Isolated voltage:
- DC/DC converter from power supply – 1000VDC
- Transceiver with transformer to network – EN61000-4-2/3/4/5/6
- Photo-coupler from Input/ Output – 5,3kVrms
- Electromagnetic compatibility: IEC 61131-2
- Dimension: max 405mm x 103mm x 110mm (for 96 I/O)
|
|
 |
PLC with up to 96 local I/O
|
 |
| Features |
- Communications – RS232/RS485, LonWorks
- Channel type – FTT 10
- Modular construction
- Up to 96 local I/O
- Scan cycle of the user program (reaction time) - Typically from 3 ms up to 10 ms.
- IEC 61131 programming
- Fast (interrupt) program ( 50 micro seconds reaction ) - 500 bytes (about a 60 steps).
- Full galvanic isolated
- Protection – IP 20
|
|
|
 |
 |
 |
 |
|